![YASKAWA CIPR-GA50C series Technical Manual Download Page 717](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765717.webp)
YASKAWA
SIEPC71061753A GA500 Technical Manual
717
Calculate the Motor Acceleration Time
Use this procedure to calculate the motor acceleration time:
1. Use
A1-02 [Control Method Selection]
to set the control method.
2. Disconnect the motor and load.
3. Run Auto-Tuning to set motor parameters.
When you cannot do Auto-Tuning, manually set motor parameters with the information on the motor
nameplate or test reports. Set the
E2 parameters
for induction motors. Set the
E5 parameters
for PM motors.
4. Set
C5 parameters [Automatic Speed Regulator (ASR)]
.
5. Set
C1-01 [Acceleration Time 1] = 0
.
6. Set
L7-01 [Forward Torque Limit]
to 100%.
7. Set the frequency reference to the same value as the motor rated speed.
8. Measure the length of time for the motor to reach the rated speed.
Show
U1-05 [Motor Speed]
on the keypad and enter the Run command (forward run).
9. Stop the motor.
10. Set
n5-02
to the measured motor acceleration time value.
Reset all of the parameters that you changed to the previous setting values.
■
n5-03: Feed Forward Control Gain
No.
(Hex.)
Name
Description
Default
(Range)
n5-03
(05B2)
Feed Forward Control Gain
Sets the ratio between load inertia and motor inertia. Inertia Tuning automatically sets the
Feedforward Control Gain value.
1.00
(0.00 - 100.00)
When you cannot do Inertia Tuning, use this procedure to set n5-03:
Set
n5-02 [Motor Inertia Acceleration Time]
.
1. Connect the motor and load.
2. Set
C1-01 [Acceleration Time 1] = 0
.
3. Use
L7-01 to L7-04 [Torque Limit]
to set the expected test run torque limit levels.
4. Set the frequency reference as specified by the high speed range of the machine.
5. Measure the length of time for the motor to reach the command reference speed.
Show
U1-05 [Motor Speed]
on the keypad and enter the Run command.
6. Stop the motor.
7. Replace the values in the this formula and set
n5-03
to the value of the formula.
•
t
accel
= Acceleration time (s)
•
f
rated
= Motor rated frequency (Hz)
•
T
Lim_Test
= Test run torque limit (%)
•
f
ref_Test
= Test run frequency reference (Hz)
WARNING!
Sudden Movement Hazard. Machinery can accelerate suddenly. Do not use this function with machinery that must
not accelerate suddenly. Sudden starts can cause serious injury or death.
Reset all of the parameters that you changed to the previous setting values.
Note:
•
If response to the speed reference is slow, increase the value set in
n5-03
.
•
Increase the value set in
n5-03
when response to the speed reference is slow.
–
The speed is overshooting.
–
A negative torque reference is output when acceleration ends.
■
n5-04: Speed Response Frequency
No.
(Hex.)
Name
Description
Default
(Range)
n5-04
(05B3)
RUN
Expert
Speed Response Frequency
Sets the response frequency for the speed reference. Usually it is not necessary to change this
parameter.
Determined by A1-02
(0.00 - 500.00 Hz)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...