7.3 List of Fault, Minor Fault, Alarm, and Error Codes
YASKAWA
SIEPC71061753A GA500 Technical Manual
241
Display (Hex.)
Name
ALM LED
Type
Ref.
Er-13
Leakage Inductance Error
Flashing
An Auto-Tuning Error
Er-14
Motor Speed Error 2
Flashing
An Auto-Tuning Error
Er-15
Torque Saturation Error
Flashing
An Auto-Tuning Error
Er-16
Inertia ID Error
Flashing
An Auto-Tuning Error
Er-17
Reverse Prohibited Error
Flashing
An Auto-Tuning Error
Er-18
Back EMF Error
Flashing
An Auto-Tuning Error
Er-19
PM Inductance Error
Flashing
An Auto-Tuning Error
Er-20
Stator Resistance Error
Flashing
An Auto-Tuning Error
Er-25
HighFreq Inject Param Tuning Err
Flashing
An Auto-Tuning Error
Err (001F)
EEPROM Write Error
Illuminated
Fault
FbH (0028)
Excessive PID Feedback
Flashing
Alarm
FbH (0041)
Excessive PID Feedback
Illuminated
Fault
FbL (0027)
PID Feedback Loss
Flashing
Alarm
FbL (0028)
PID Feedback Loss
Illuminated
Fault
GF (0006)
Ground Fault
Illuminated
Fault
HCA (0034)
High Current Alarm
Flashing
Alarm
iFEr
Communication Err
-
Backup Function Runtime Errors
L24v (0021)
Loss of External Power 24 Supply
Flashing
An alarm
LF (001C)
Output Phase Loss
Illuminated
Fault
LF2 (0036)
Output Current Imbalance
Illuminated
Fault
LoG
Log Com Error
Flashing
An alarm
LSo (0051)
Low Speed Motor Step-Out
Illuminated
Fault
LT-1 (0035)
Cooling Fan Maintenance Time
Flashing
An alarm
LT-2 (0036)
Capacitor Maintenance Time
Flashing
An alarm
LT-3 (0043)
SoftChargeBypassRelay MainteTime
Flashing
An alarm
LT-4 (0044)
IGBT Maintenance Time (50%)
Flashing
An alarm
ndAT
Model,VolClass,Capacity Mismatch
-
Backup Function Runtime Errors
nSE (0052)
Node Setup Error
Illuminated
Fault
oC (0007)
Overcurrent
Illuminated
Fault
oFA00 (0101)
Option Not Compatible with Port
Illuminated
Fault
oFA03 - oFA06 (0104 - 0107)
Option Card Error Occurred at Option Port (CN5)
Illuminated
Fault
oFA10, oFA11 (0111, 0112)
Option Card Error Occurred at Option Port (CN5)
Illuminated
Fault
oFA12 - oFA17 (0113 - 0118)
Option Card Connection Error (CN5)
Illuminated
Fault
oFA30 - oFA43 (0131 - 013E)
Communication Option Card Connection Error (CN5)
Illuminated
Fault
oH (0003)
Heatsink Overheat
Flashing
Alarm
oH (0009)
Heatsink Overheat
Illuminated
Fault
oH1 (000A)
Heatsink Overheat
Illuminated
Fault
oH2 (0004)
External Overheat (H1-XX=B)
Flashing
Alarm
oH3 (001D)
Motor Overheat (PTC Input)
Illuminated
Fault
oH3 (0022)
Motor Overheat (PTC Input)
Flashing
Alarm
oH4 (0020)
Motor Overheat Fault (PTC Input)
Illuminated
Fault
oL1 (000B)
Motor Overload
Illuminated
Fault
oL2 (000C)
Drive Overload
Illuminated
Fault
oL3 (0005)
Overtorque 1
Flashing
Alarm
oL3 (000D)
Overtorque Detection 1
Illuminated
Fault
oL4 (0006)
Overtorque 2
Flashing
Alarm
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...