254
YASKAWA
SIEPC71061753A GA500 Technical Manual
Code
Name
Causes
Possible Solutions
There is increased motor loss from overexcitation
operation.
•
Lower the value set in
n3-13 [OverexcitationBraking (OEB)
Gain]
.
•
Set
L3-04 ≠ 4 [Stall Prevention during Decel ≠ Overexcitation/
High Flux]
.
•
Set
n3-23 = 0 [Overexcitation Braking Operation = Disabled]
.
The speed search-related parameters are set
incorrectly.
•
Examine the settings for all speed search related parameters.
•
Adjust
b3-03 [Speed Search Deceleration Time]
.
•
Set
b3-24 = 1 [Speed Search Method Selection = Speed
Estimation]
after Auto-Tuning.
Phase loss in the input power supply is causing the
output current to change.
Make sure that there is no phase loss, and repair problems.
The motor main circuit cable is too long.
•
Replace the drive with a larger capacity model.
•
Decrease
C6-02 [Carrier Frequency]
. Or set
C6-02 = B
.
Note:
•
The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
•
Do a Fault Reset to clear the fault.
•
L5-07 [Fault Reset Enable Select Grp1]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oL2
Drive Overload
The load is too large.
Decrease the load.
The acceleration/deceleration times or cycle times
are too short.
•
Examine the acceleration/deceleration times and the motor
start/stop frequencies (cycle times).
•
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Times]
.
The V/f pattern does not fit the motor qualities.
•
Examine the ratios between the V/f pattern frequency and
voltage. Decrease the voltage if it is too high compared to the
frequency.
•
Adjust
E1-04 to E1-10 [V/f Pattern Parameters]
. Decrease the
values set in
E1-08 [Mid Point A Voltage]
and
E1-10
[Minimum Output Voltage]
. For motor 2, adjust
E3-04 to E3-
10
.
Note:
If the values set in
E1-08
and
E1-10
are too low, the overload
tolerance will decrease at low speeds.
The drive capacity is too small.
Replace the drive with a larger capacity model.
Overload occurred while running at low speed.
•
Decrease the load when running at low speed.
•
Replace the drive with a larger capacity model.
•
Decrease the value set in
C6-02 [Carrier Frequency
Selection]
.
The torque compensation gain is too large.
Decrease the value set in
C4-01 [Torque Compensation Gain]
to
make sure that the motor does not stall.
The speed search-related parameters are set
incorrectly.
•
Examine the settings for all speed search-related parameters.
•
Adjust
b3-03 [Speed Search Deceleration Time]
.
•
Set
b3-24 = 1 [Speed Search Method Selection = Speed
Estimation]
after Auto-Tuning.
Phase loss in the input power supply is causing the
output current to change.
•
Correct errors with the wiring for main circuit drive input
power.
•
Make sure that there is no phase loss, and repair problems.
Overload occurred during overexcitation
deceleration.
•
Decrease the value set in
n3-13 [OverexcitationBraking (OEB)
Gain]
.
•
Decrease the value set in
n3-21 [HSB Current Suppression
Level]
.
Note:
•
The drive detects this fault if the electronic thermal protector of the drive started the drive overload protection.
•
Do a Fault Reset to clear the fault.
•
L5-07 [Fault Reset Enable Select Grp1]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oL3
Overtorque Detection 1
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-02 [Torque Detection Level 1]
and
L6-03 [Torque
Detection Time 1]
settings.
Note:
•
The drive detects this fault if the drive output current is more than the level set in
L6-02
for longer than
L6-03
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L6-01 [Torque Detection Selection 1]
.
•
L5-07 [Fault Reset Enable Select Grp1]
disables the Auto Restart function.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...