![YASKAWA CIPR-GA50C series Technical Manual Download Page 697](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765697.webp)
YASKAWA
SIEPC71061753A GA500 Technical Manual
697
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an
oL3 [Overtorque Detection 1]
and operation
continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an
oL3
and
operation continues.
3 : oL @ Speed Agree - Fault
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an
oL3 [Overtorque Detection 1]
and operation stops.
4 : oL @ RUN - Fault
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an
oL3
and
operation stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a
UL3 [Undertorque Detection 1]
and operation
continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a
UL3
and
operation continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a
UL3
and operation stops.
8 : UL @ RUN - Fault
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a
UL3
and
operation stops
■
L6-02: Torque Detection Level 1
No.
(Hex.)
Name
Description
Default
(Range)
L6-02
(04A2)
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
•
Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
•
You can also use an analog input terminal to supply the torque detection level. To enable this function, set
H3-xx = 7 [MFAI Function
Select = Overtorque/Undertorque DetectLvl]
. If you set
L6-02
and
H3-x = 7
, the analog input is most important and the drive disables
L6-02
.
■
L6-03: Torque Detection Time 1
No.
(Hex.)
Name
Description
Default
(Range)
L6-03
(04A3)
Torque Detection Time 1
Sets the detection time for Overtorque/Undertorque Detection 1.
0.1 s
(0.0 - 10.0 s)
■
L6-04: Torque Detection Selection 2
No.
(Hex.)
Name
Description
Default
(Range)
L6-04
(04A4)
Torque Detection Selection
2
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0
(0 - 8)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-05 [Torque
Detection Level 2]
for the length of time set in
L6-06 [Torque Detection Time 2]
. The drive detects undertorque if
the motor current or output torque is less than the level set in
L6-05
for the length the time set in
L6-06
.
0 : Disabled
The drive will not detect overtorque or undertorque.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...