12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
619
The drive will short circuit the three phases of a PM motor to cause braking torque in the spinning motor.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
•
Refer to "b2: DC Injection Braking and Short Circuit Braking" for more information.
ON : Short Circuit Braking is enabled.
OFF : Normal operation
■
7D: Short Circuit Braking (N.C.)
Setting Value
Function
Description
7D
Short Circuit Braking
(N.C.)
Sets operation of Short Circuit Braking (N.C.).
The drive will short circuit the three phases of a PM motor to cause braking torque in the spinning motor.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
•
Refer to "b2: DC Injection Braking and Short Circuit Braking" for more information.
ON : Normal operation
OFF : Short Circuit Braking is enabled.
■
7E: Reverse Rotation Identifier
Setting Value
Function
Description
7E
Reverse Rotation Identifier
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
ON : Reverse run
The drive knows that the motor is rotating in the reverse direction.
OFF : Forward run
The drive knows that the motor is rotating in the forward direction.
■
7F: PID Bi-Directional Enable
Setting Value
Function
Description
7F
PID Bi-Directional Enable
Sets operation of the PID Bi-Directional function.
ON : Enabled
OFF : Disabled
■
90 to 96: DWEZ Digital Inputs 1 to 7
Setting Value
Function
Description
90 - 96
DWEZ Digital Inputs 1 to 7
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Note:
You cannot set values 90 to 96 for inverse output.
■
9F: DWEZ Disable
Setting Value
Function
Description
9F
DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
Note:
Set
A1-07 = 2 [DriveWorksEZ Function Selection = Digital input]
to use this function.
ON : Disabled
OFF : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...