702
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
L7-06: Torque Limit Integral Time
No.
(Hex.)
Name
Description
Default
(Range)
L7-06
(04AC)
Torque Limit Integral Time
Sets the integral time constant for the torque limit function.
200 ms
(5 - 10000 ms)
Decrease the setting value to increase torque limit responsiveness when you use torque limits and
L7-07 = 1
[Torque Limit during Accel/Decel = Proportional & Integral control]
.
If there is hunting when torque limits are active, increase the setting value.
■
L7-07: Torque Limit during Accel/Decel
No.
(Hex.)
Name
Description
Default
(Range)
L7-07
(04C9)
Torque Limit during Accel/
Decel
Sets the torque limit function during acceleration and deceleration.
0
(0, 1)
0 : Proportional only
The torque limit function works with proportional control during acceleration and deceleration, and switches to
integral control at constant speed. Use this setting when quickly reaching the target speed is more important than
the torque limit during speed changes.
1 : Proportional & Integral control
The torque limit function always uses integral control. Use this setting when a very accurate torque limit is
necessary during speed changes, for example in winding machine applications.
If you make the torque limit the most important, it can:
•
Increase the acceleration and deceleration times.
•
Not let the motor speed reach the frequency reference value during run at constant speed.
■
L7-16: Torque Limit Process at Start
No.
(Hex.)
Name
Description
Default
(Range)
L7-16
(044D)
Torque Limit Process at
Start
Assigns a time filter to allow the torque limit to build at start.
1
(0, 1)
0 : Disabled
There is torque limit at start without a delay time.
Use this setting to maximize the response time when sudden acceleration or deceleration at start is necessary.
1 : Enabled
There is a delay time of 64 ms at start to build the torque limit.
◆
L8: Drive Protection
L8 parameters
set protective functions that prevent faults such as overheating, phase loss, and ground faults.
■
L8-01: 3% ERF DB Resistor Protection
No.
(Hex.)
Name
Description
Default
(Range)
L8-01
(04AD)
3% ERF DB Resistor
Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0
(0, 1)
0 : No
Disables braking resistor protection. Use this setting for dynamic braking options that are not Yaskawa ERF series
braking resistors.
1 : Yes
Enables protection for Yaskawa ERF series braking resistors.
Note:
Set
L8-01 = 1
and
H2-01 to H2-03 = D [MFDO Function Select = Braking Resistor Fault]
. Use a sequence to turn OFF power with
MFDO.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...