![YASKAWA CIPR-GA50C series Technical Manual Download Page 710](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765710.webp)
710
YASKAWA
SIEPC71061753A GA500 Technical Manual
12.10 n: Special Adjustment
n parameters
set these functions:
•
Function to prevent hunting
•
High-slip braking
•
Motor line-to-line resistance online tuning
•
Fine-tune the parameters that adjust motor control
◆
n1: Hunting Prevention
The Hunting Prevention function will not let low inertia or operation with a light load cause hunting. Hunting
frequently occurs when you have a high carrier frequency and an output frequency less than 30 Hz.
■
n1-01: Hunting Prevention Selection
No.
(Hex.)
Name
Description
Default
(Range)
n1-01
(0580)
Hunting Prevention
Selection
Sets the function to prevent hunting.
0
( 0, 1 )
Note:
When you replace a V1000-series drive with a GA500 drive, set
n1-01 = 1 [Hunting Prevention Selection = Enabled]
.
When drive response is more important than the decrease of motor vibration, disable this function.
0 : Disable
1 : Enabled
■
n1-02: Hunting Prevention Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
n1-02
(0581)
Expert
Hunting Prevention Gain
Setting
Sets the performance of the hunting prevention function. Usually it is not necessary to change this
parameter.
1.00
(0.00 - 2.50)
Adjust this parameter in these conditions:
•
When
n1-01 = 1 [Hunting Prevention Selection = Enabled (Normal)]
, if oscillation occurs when you operate a
motor with a light load, increase the setting value in 0.1-unit increments.
•
When
n1-01 = 2
, if the motor stalls, decrease the setting value in 0.1-unit increments.
■
n1-03: Hunting Prevention Time Constant
No.
(Hex.)
Name
Description
Default
(Range)
n1-03
(0582)
Expert
Hunting Prevention Time
Constant
Sets the primary delay time constant of the hunting prevention function. Usually it is not
necessary to change this parameter.
Determined by o2-04
(0 - 500 ms)
Adjust this parameter in these conditions:
•
Load inertia is large: Increase the setting value. If the setting value is too high, response will be slower. Also,
there will be oscillation when the frequency is low.
•
Oscillation occurs at low frequencies: Decrease the setting value.
■
n1-05: Hunting Prevent Gain in Reverse
No.
(Hex.)
Name
Description
Default
(Range)
n1-05
(0530)
Expert
Hunting Prevent Gain in
Reverse
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run.
Usually it is not necessary to change this parameter.
0.00
(0.00 - 2.50)
Note:
When you set
n1-05 = 0
, the value set in
n1-02 [Hunting Prevention Gain Setting]
is effective when the motor rotates in reverse.
Adjust this parameter in these conditions:
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...