11.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA
SIEPC71061753A GA500 Technical Manual
431
11.21 Defaults by Drive Model and Duty Rating ND/HD
The values for the parameters in these tables depend on the values for parameters
o2-04
and
C6-01
. Changing the
settings for
o2-04
and
C6-01
will change the default settings.
◆
Three-Phase 200 V Class
No.
Name
Unit
Default
-
Drive Model
-
2001
2002
2004
2006
C6-01
Normal /
Heavy Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model
(KVA)
Selection
Hex.
60
61
62
63
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
b3-04
V/f Gain
during Speed
Search
%
100
100
100
100
100
100
100
100
b3-06
Speed
Estimation
Current Level
1
-
1
1
1
1
1
1
0.5
0.5
b3-08
Speed
Estimation
ACR P Gain
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-26
Direction
Determination
Level
-
1000
1000
1000
1000
1000
1000
1000
1000
b8-03
Energy Saving
Filter Time
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
Energy Saving
Coefficient
Value
-
481.7
356.9
356.9
288.2
288.2
223.7
223.7
196.6
C6-02
Carrier
Frequency
Selection
-
4
7
4
7
4
7
4
7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A
0.6
1.1
1.1
1.9
1.9
3.3
3.3
4.9
E2-02
(E4-02)
Motor Rated
Slip
Hz
2.5
2.6
2.6
2.9
2.9
2.5
2.5
2.6
E2-03
(E4-03)
Motor No-
Load Current
A
0.4
0.8
0.8
1.2
1.2
1.8
1.8
2.3
E2-05
(E4-05)
Motor Line-
to-Line
Resistance
Ω
35.98
20.56
20.56
9.842
9.842
5.156
5.156
3.577
E2-06
(E4-06)
Motor
Leakage
Inductance
%
21.6
20.1
20.1
18.2
18.2
13.8
13.8
18.5
E2-10
(E4-10)
Motor Iron
Loss
W
6
11
11
14
14
26
26
38
E5-01
PM Motor
Code
Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Power Loss
Ride Through
Time
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
L2-03
Minimum
Baseblock
Time
s
0.2
0.3
0.2
0.3
0.2
0.3
0.3
0.4
L2-04
Powerloss V/f
Recovery
Ramp Time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
-
190
190
190
190
190
190
190
190
L3-02
Stall Prevent
Level during
Accel
%
150
120
150
120
150
120
150
120
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...