Parameter Setting Errors
Parameter setting errors occur when multiple parameter settings do not agree, or when parameter setting values
are not correct. Refer to the table in this section, examine the parameter setting that caused the error, and remove
the cause of the error. You must first correct the parameter setting errors before you can operate the drive. The
drive will not send notification signals for the faults and alarms when these parameter setting errors occur.
Code
Name
Causes
Possible Solutions
oPE01
Drive Capacity Setting Error
The value set in
o2-04 [Drive Model (KVA)
Selection]
does not agree with the drive model.
Set
o2-04
to the correct value.
Code
Name
Causes
Possible Solutions
oPE02
Parameter Range Setting Error
Parameters settings are not in the applicable setting
range.
1.
Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
Set
E2-01 ≤ E2-03 [Motor Rated Current (FLA) ≤
Motor No-Load Current]
.
Make sure that
E2-01 > E2-03
.
Note:
If it is necessary to set
E2-01 < E2-03
, first lower the value
set in
E2-03
, and then set
E2-01
.
Code
Name
Causes
Possible Solutions
oPE03
Multi-Function Input Setting Err
The settings for these parameters do not agree:
•
H1-01 to H1-07 [Terminals S1 to S8 Function
Selection]
•
H7-01 to H7-04 [Virtual Multi-Function Inputs 1
to 4]
Correct the parameter settings.
The settings for MFDIs overlap.
Note:
This does not include
H1-xx = 20 to 2F [MFDI
Function Select = External Fault]
and
[Reserved]
.
Set the parameters correctly to prevent MFDI function overlap.
These pairs of MFDI functions are not set to Digital
Inputs (
H1-xx
and
H7-01 to H7-04
) at the same
time:
•
Setting values
10 [Up Command]
and
11 [Down
Command]
•
Setting values
75 [Up 2 Command]
and
76
[Down 2 Command]
•
Setting values
42 [Run Command (2-Wire
Sequence 2)]
and
43 [FWD/REV (2-Wire
Sequence 2)]
Set the MFDI pairs.
A minimum of two of these MFDI combinations are
set to Digital Inputs (
H1-xx
and
H7-01 to H7-04
) at
the same time:
•
Setting values
10 [Up Command]
and
11 [Down
Command]
•
Setting values
75 [Up 2 Command]
and
76
[Down 2 Command]
•
Setting value
A [Accel/Decel Ramp Hold]
•
Setting value
1E [Reference Sample Hold]
•
Setting values
44 to 46 [Add Offset Frequency 1
to 3 (d7-01 to d7-03)]
Remove the function settings that are not in use.
These commands are set in Digital Inputs (
H1-xx
and
H7-01 to H7-04
) at the same time:
•
Setting values
61 [Speed Search from Fmax]
and
62 [Speed Search from Fref]
•
Setting values
65, 66, 7A, 7B [KEB Ride-Thru 1
or 2 Activate]
and
68 [High Slip Braking (HSB)
Activate]
•
Setting values
16 [Motor 2 Selection]
and
1A
[Accel/Decel Time Selection 2]
•
Setting values
65, 66 [KEB Ride-Thru 1
Activate]
and
7A, 7B [KEB Ride-Thru 2
Activate]
•
Setting values
40, 41 [Forward RUN (2-Wire),
Reverse RUN (2-Wire)]
and
42, 43 [Run
Command (2-Wire Sequence 2), FWD/REV (2-
Wire Sequence 2)]
•
Setting values
60 [DC Injection Braking
Command]
and
6A [Drive Enable]
•
Setting values
16 [Motor 2 Selection]
and
75, 76
[Up 2 Command, Down 2 Command]
Remove the function settings that are not in use.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...