![YASKAWA CIPR-GA50C series Technical Manual Download Page 621](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765621.webp)
12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
621
Setting Value
Function
Reference
66
Comparator1
67
Comparator2
69
External Power 24V Supply
6A
Data Logger Error
Setting Value
Function
Reference
90 - 92
DWEZ Digital Output 1 to 3
100 - 192
Inverse output of 0 to 92
Sets an inverse output of the function for
the MFDO. Put a 1 at the front of the
function setting to set inverse output. For
example, set
138
for inverse output of
38
[Drive Enabled]
.
*1
Inverse output is not available.
■
Extend MFDO1 to MFDO3 Function Selection
You can set MFDO functions to
bit 0 to bit 2 [MEMOBUS MFDO1 to 3]
of MEMOBUS register 15E0 (Hex.).
Use
H2-40 to H2-42 [Mbus Reg 15E0h bit0 to bit2 Output Func]
to select the function.
Figure 12.73 Functional Block Diagram of MEMOBUS Multi-function Output
Table 12.62 MEMOBUS MFDO Registers
Register No.
(Hex.)
Name
15E0
bit0
MEMOBUS MFDO 1
bit1
MEMOBUS MFDO 2
bit2
MEMOBUS MFDO 3
Note:
•
Refer to H2-xx
“
MFDO Setting Values
”
for more information about MFDO setting values.
•
When you do not set functions to
H2-40 to H2-42
, set them to
F
.
■
Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use
H2-60, H2-63, and H2-66 [Term MA,MB,MC Secondary Function, Terminal P1 Secondary Function, and
Terminal P2 Secondary Function]
to set the function of the output signal for which you will perform logical
operations.
Use
H2-61, H2-64, and H2-67 [Term MA,MB,MC Logical Operation, Terminal P1 Logical Operation, and
Terminal P2 Logical Operation]
to set the logical operation.
Figure 12.74 Functional Block Diagram of Logical Operation Output for MFDO 1
Table 12.63 MFDO Logical Operation Table
Logical Operation Selection
Logical Operation Expression
Logical Operation Notation
H2-61, H2-64, H2-67
0
A=B=1
1
A=1 or B=1
2
A=0 or B=0
3
A=B=0
4
A=B
A=B
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...