HallSeq
Hall Sequence
error.
The hall sensor outputs
have an invalid value
(111 or 000), or the
sequence between the
current state and the last
state is invalid.
0x7303,
0x7304
Please check the wiring and make
sure that the signals are transfered
with good consistency.
If the HALL sensor is used together
with an incremental encoder for
commutation, it can be that the
HALL sensor A/B/C pins are
connected in a wrong order. Please
verify the cabling, and verify the
order by running offset detection
with only the HALL sensor
configured for commutation. If the
order is correct, the result of the
offset detection should be around
0, and 0x2003:5 Motor phases
inverted should show 0 (No).
A-Format sensor faults
AftFrame
A-Format
Frame error.
The fixed data in the
recieved A-Format frame
(like sync code) is wrong.
This usually means that
the A-Format
transmission speed is
wrong.
0x7303,
0x7304
Please check the transmission
speed configuration according to
the encoder datasheet.
AftTmout
A-Format
Timeout.
The A-Format encoder
didn't start
communication after
sending a request.
0x7303,
0x7304
Please check the wiring and make
sure that the signals are transfered
with good consistency. Use a
oscilloscope to monitor the signal
transfered for further
investigation.
AftCrc
A-Format CRC
error.
The A-Format frame
contains a CRC of some
of the data that is being
sent. This error is raised
when the CRC sent by
the encoder is different
than the CRC computed
by the drive. This usually
means that the drive
can't read the frame
properly, which usually
happens because of
noise in the
communication link.
0x7303,
0x7304
Please check the signals received
by the drive with an oscilloscope
under operation for better
investigation. The cause can be
that the signal transfer is
influenced by external field, or that
the signal transfer is unstable for
example due to soldering quality
or cable aging. Improve the
situation by replacing the cables,
better arranging the cables, adding
shielding, etc., ensuring that the
signals can be stably transfered
with acceptable noise.