09.2008
Communication / PROFIBUS
Siemens AG
6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES
Compendium Motion Control
8.2-119
8.2.10.2
Fault and alarm display on the basic unit
If faults occur during communication between the PROFIBUS and the
CBP, corresponding fault or alarm messages are displayed on the PMU
or on the OP of the basic unit.
Alarm number
Meaning
First
CB/TB
Second
CB
A 081
A 089
The ID byte combinations sent by the DP master in the
configuration telegram do not correspond with the
permitted ID byte combinations (see table 8.2-12)
Consequence:
No connection established with the PROFIBUS-DP
master; new configuration is necessary.
A 082
A 090
No valid PPO type can be established from the
configuration telegram from the DP master.
Consequence:
No connection established with the PROFIBUS-DP
master, new configuration is necessary.
A 083
A 091
No net data or invalid net data (e.g. complete control
word STW1=0) are being received by the DP master.
Consequence:
The process data are not being transferred to the DPR.
If parameter P722 (P695) is not equal to zero, this will
result in fault message F 082 being tripped (see
chapter "Process data monitoring".
A 084
A 092
Telegram traffic between DP master and CBP has
been interrupted (e.g. cable break, bus connector
disconnected or DP master switched off).
Consequence:
If parameter P722 (P695) is not equal to zero, this will
result in fault message F 082 being tripped (see
chapter "Process data monitoring").
A 086
A 094
Failure of heartbeat counter recognized by basic unit.
Consequence:
Interruption of communication to the automation system
A 087
A 095
DP slave software detects serious fault. Fault number
in diagnostic parameter r732.8
Consequence:
Communication no longer possible. Secondary fault
F082
Alarms