![Siemens simovert masterdrives Compendium Download Page 530](http://html.mh-extra.com/html/siemens/simovert-masterdrives/simovert-masterdrives_compendium_378171530.webp)
Communication / CBC
03.2010
6SE7087-6QX70 (Version AL) Siemens AG
8.4-32
Compendium Motion Control
SIMOVERT MASTERDRIVES
8.4.5.1
Basic parameterization of the units
Optional boards?
P060 = 4
P711 = 0...2000
no
yes
Possible optional boards: CBC, CBP, TB
Basis identifier for PKW task / PKW reply
P722 = 0...65535
P053 = x
Function selection "hardware configuration"
P712 = 0...2000
Basis identifier for PZD-receive
P713 = 0...2000
P714 = 1...16
Number of PZDs for PZD-send
P715 = 0...65535
Update rate for PZD-send
P716 = 0...2000
Basis identifier for PZD-receive broadcast
P717 = 0...2000
Basis identifier for PZD-receive mulitcast
P718 = 0...2000
Basis identifier for PZD-receive cross transfer
P719 = 0...2000
Basis identifier for PZD-request broadcast
P720 = 0...8
Baud rate
P721.01 = 0
CAN-profile (at the present only 0 possible) (optional)
P721.02 =
0...65535
Bus timing (optional)
P918 = n
CBC bus address (0
≤
n < 128)
P060 = 0
Leave "hardware configuration"
P060 = 5
For setting the telegram failure time in ms
(0 = deactivated)
Parameterization enable CBC
Function selection "drive setting"
Basis identifier for PZD-send
Fig. 8.4-16
Parameterization of the "hardware configuration" for MASTERDRIVES
with CUPM, CUMC or CUVC
Basic
parameterization for
MASTERDRIVES
with CUPM, CUMC
or CUVC