Number / Fault
Cause
Counter-measure
F058
Parameter fault
Parameter task
A fault has occurred during the processing of a
parameter task.
No remedy
F059
Parameter fault after
factory setting/init.
A fault has occurred in the initialization phase
during the calculation of a parameter.
The number of the inconsistent parameter is
indicated in fault value r949. Correct this
parameter (ALL indices) and switch voltage off
and on again. Several parameters may be
affected, i.e. repeat process.
F060
MLFB is missing during
initial loading
Is set if parameter P070 is at zero when
INITIAL LOADING is exited.
Enter correct MLFB after acknowledging the
fault (power section, initial loading)
F061
Incorrect
parameterization
A parameter which has been entered during
drive setting is in the non-permissible range.
The number of the inconsistent parameter is
indicated in fault value r949 (e.g. motor
enocder = pulse encoder in the case of
brushless DC motors) -> correct this
parameter.
F063
PIN is missing
The synchronization or positioning technology
functions have been activated without an
authorization being present (PIN)
- Deactivate synchronization or positioning
- Enter the PIN (U2977)
If technology functions are inserted in the time
slots without enabling the technology function
through the PIN, the message F063 is
generated. This fault can only be cleared by
putting in the correct PIN at U977.01 and
U977.02 and switching the power off and on
again, or by disabling the technology functions
(put U953.32 = 20 and U053.33 = 20).
F065
SCom telegram failure
No telegram has been received at an SCom
interface (SCom/USS protocol) within the
telegram failure time.
Fault value r949:
1 = Interface 1 (SCom1)
2 = Interface 2 (SCom2)
Check the connection of PMU -X300 or
X103 / 27,28 (Compact, chassis unit)
Check the connection of X103 or X100 / 35,36
(Compact PLUS unit)
Check "SCom/SCB TlgOff" P704.01 (SCom1)
or P704.02 (SCom2)
F070
SCB initialization fault
A fault has occurred during initialization of the
SCB board.
Fault value r949:
1: Board code incorrect
2: SCB board not compatible
5: Error in configuration data
(Check parameterization)
6: Initialization timeout
7: SCB board double
10: Channel error
F072
EB initialization fault
A fault has occurred during initialization of the
EB board.
Fault value r949:
2: 1st EB1 not compatible
3: 2nd EB1 not compatible
4: 1st EB2 not compatible
5: 2nd EB2 not compatible
21: Three EB1 boards
22: Three EB2 boards
110: Fault on 1st EB1
120: Fault on 2nd EB1
210: Fault on 1st EB2
220: Fault on 2nd EB2
F073
AnInp1SL1
not Compact PLUS
4 mA at analog input 1, slave 1 fallen short of
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 4, 5.