Function diagram
8
7
6
5
4
3
2
1
fp_mc_122_e.vsd
PROFIBUS CBP2
MASTERDRIVES MC
23.10.02
Synchronizing
- 122 -
V2.5
Synchronizing
PLL
[420.5]
Pulse frequency
1
Alarm A003 "not synchronous"
(with transceiver)
(Dispatcher only)
Only allowed for PWE 2 or 20 (inactive).
Fine synchronization
r748.001:
Number of error-free synchronizing telegrams
.002:
Unassigned
.003:
Unassigned
.004:
Unassigned
.005:
Unassigned
.006:
Unassigned
.007:
Unassigned
.008:
Unassigned
.009:
Synchronism deviation
(65535 Synchronization not active)
permissible deviation between 65515 and 20
.010:
Corrected pulse period in units of 100 ns
.011:
T0 counter (0 with active synchronization)
.012:
Internal
.013:
Internal
.014:
Time counter
.015:
Implemented bus cycle time
.016:
Internal
Diagnosis
PROFIBUS
synchronization
Fine synchronization can cause a smaller
synchronization deviation (r748.9).
Fine synchronization has a greater effect the
higher the DP cycle/T2 ratio.
n959.22 = 4
Maximum
synchronized
time slot
0...10
P754 (0)
K
P753 (0)
Sync time counter
PROFIBUS
cycle time
r748.15
B0043
Drive in synchronism
K0260
Time counter
U950.22 = ___(20)
SLB Diagnosis
r748