Parameter
Description
Data
Read/write
P799*
S.OFF ActV
799
BICO parameter for selecting the connector from which
the actual value for generating the firing-pulse block is to
be read in. If the actual value falls below the shut-down
value (P800) after an OFF command, the firing pulse is
blocked. Preferably, the actual speed (KK0091) is
selected as the actual value.
Init: 91
Unit: -
Indices: -
Type: L2 ,K
Menus:
- Parameter menu
+ Diagnostics
+ Messages/displays
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P800
OFF Value
800
Function parameter for entering the turn-off value below
which the firing-pulse block is to be generated. If the
actual value falls below the turn-off value after an OFF
command, the firing pulses are blocked. The firing-pulse
block can be delayed by the time entered in P801.
In function diagram 480.3
index1: 0,5
Min: 0,0
Max: 200,0
Unit: %
Indices: 4
,FDS
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Messages/displays
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P801
OFF Time
801
Function parameter for entering the time by which the
firing-pulse block is to be delayed. If the actual value falls
below the turn-off value after an OFF command, blocking
of the firing pulses is delayed by the time entered.
In function diagram: 480.5
index1: 0,00
Min: 0,00
Max: 100,00
Unit: s
Indices: 4
,FDS
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Messages/displays
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P802*
S.Speed Setp
802
BICO parameter for selecting the connector from which
the speed setpoint is to be read in for detecting the
direction of rotation. Preferably, the speed setpoint
KK0150) is used. The message "Positive speed setpoint"
is indicated in status word 1, bit 14.
Init: 150
Unit: -
Indices: -
Type: L2 ,K
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P803*
S.Speed ActV
803
BICO parameter for selecting the connector from which
the actual speed is to be read in for detecting overspeed.
Preferably, the actual speed (KK0091) is used. The
message "Overspeed" is indicated in status word 2, bit 18.
Init: 91
Unit: -
Indices: -
Type: L2 ,K
Menus:
- Parameter menu
+ Diagnostics
+ Messages/displays
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P805
PullOut/BlckTime
805
Waiting time after "Setpoint/actual deviation" message
(status word 1, bit 8) during blocking up to output of a fault
message (r553 bit28).
Dependent parameters:
P790 (Source setpoint of the setpoint/actual
deviation)
P791 (Source actual value of setpoint/actual
deviation)
P792 (Frequency of setpoint/actual deviation),
P794 (Duration of setpoint/actual deviation)
Init: 50,00
Min: 0,00
Max: 100,00
Unit: s
Indices: -
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Messages/displays
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P806
Fct BlockOverl
806
Setting the stall or blocking diagnosis
n-control
0 Complete blocking diagnosis (incl. overload diagnosis at
n=0)
1 Only blocking diagnosis (at n=0)
2 Function completely deselected
v/f characteristic
0 Stall diagnosis selected
1 Stall diagnosis selected
2 Function deselected
Init: 0
Min: 0
Max: 2
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Messages/displays
- Upread/free access
Changeable in:
- Ready to switch on
105
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control