Communication / CBC CANopen Communication Board
Siemens AG
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
Compendium Motion Control
8.5-17
P053 (enable parameterization))
Parameter P053 (see also "Parameter List" in converter operating guide)
must be set to an uneven number (e.g. 1, 3, 7 etc.). This parameter defines
the sources (e.g. PMU, CBC, etc.) from which parameters may be modified.
The CBC requires this enable setting to be able to execute SDO tasks.
Example: P053 = 1: Parameterization enable for CBC only
= 3: Parameterization enable for CBC+PMU
= 7: Parameterization enable for CBC+PMU+SST1 (OP)
The parameter modification enable must be set via the CBC (P053 = 1, 3
etc.) before any other parameter settings can be altered via SDO tasks from
the CAN bus master.
P060 (menu selection)
P60 = 4 Select "Board configuration" function
P60 = 5 Select "Board configuration and drive setting" function