Parameter
Description
Data
Read/write
P040*
S.Disp SpdConn
40
BICO parameter for selecting connectors which contain a
speed and are to be displayed in visualization parameter
r041 in [1/min]. The connector numbers entered in the
respective index are displayed in the same index of
parameter r041.
In function diagram:
30.7
index1: 0
Unit: -
Indices: 5
Type: L2 ,K
,K
Menus:
- Parameter menu
+ General parameters
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r041
Disp Speed Conn
41
Visualization parameter for the display of connectors
given in P040 in [1/min]. The connectors displayed in the
respective index have been selected in the same index of
parameter P040. The normalization is specified in P353.
The following method of calculation must be used: r041 =
P353 xConnector Value in [%]/100%.
In function diagram:
30.8
Dec.Plc.: 1
Unit: 1/min
Indices: 5
Type: I4
Menus:
- Parameter menu
+ General parameters
- Upread/free access
P042*
S.DispFreqConn
42
BICO parameter for selecting connectors which contain a
frequency and are to be displayed in visualization
parameter r043 in [Hz]. The connector numbers entered in
the respective index are displayed in the same index of
parameter r043.
In function diagram:
30.7
index1: 0
Unit: -
Indices: 5
Type: L2 ,K
,K
Menus:
- Parameter menu
+ General parameters
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r043
Disp Freq Conn
43
Visualization parameter for the display of connectors
given in P042 in [Hz]. The connectors displayed in the
respective index have been selected in the same index of
parameter P042. The normalization is specified in P352.
The following method of calculation must be used:
r043 = P352 x Connector Value in [%]/100%.
In function diagram:
30.8
Dec.Plc.: 2
Unit: Hz
Indices: 5
Type: I4
Menus:
- Parameter menu
+ General parameters
- Upread/free access
P044*
S.Disp DecConn
44
BICO parameter for selecting connectors which are to
displayed in visualization parameter r045 as an integral
decimal number preceded by a plus or minus sign. The
connector numbers entered in the respective index are
displayed in the same index of parameter r045.
In function diagram:
30.1
index1: 0
Unit: -
Indices: 5
Type: L2 ,K
,K
Menus:
- Parameter menu
+ General parameters
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r045
Disp DecConn
45
Visualization parameter for the display of connectors
given in P044 as an integral whole decimal number. The
connectors displayed in the respective index have been
selected in the same index of parameter P044.
In function diagram:
30.2
Dec.Plc.: 0
Unit: -
Indices: 5
Type: I4
Menus:
- Parameter menu
+ General parameters
- Upread/free access
P046*
S.Disp HexConn
46
BICO parameter for selecting connectors which are to be
displayed in visualization parameter r047as an integral
value (hexadecimal). The connector numbers entered in
the respective index are displayed in the same index of
parameter r047.
In function diagram:
30.1
index1: 0
Unit: -
Indices: 5
Type: L2 ,K
,K
Menus:
- Parameter menu
+ General parameters
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
5
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control