Parameter
Description
Data
Read/write
r930
Operating Mode
930
Profibus-specific parameter
The parameter indicates the mode of operation to
PROFIdrive V3
Dec.Plc.: 0
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
- Upread/free access
r944
Fault Counter
944
The fault counter is incremented each time there is a
change in the fault buffer (P947, P948, P782). This allows
a check to be performed on whether data in the fault
buffer is being extracted consistently.
Dec.Plc.: 0
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
- Drive setting
- Upread/free access
r947
Fault Memory
947
Visualization parameter for displaying the last 8 fault trips.
For each fault trip, up to 8 faults occurring at the same
time can be stored. Only those faults are stored to which
a fault number is assigned.
Index 1 to 8: 1st (last) fault trip, faults 1 to 8
Index 9 to 16: 2nd fault trip, faults 1 to 8
Index 17 to 24: 3rd fault trip, faults 1 to 8
Index 25 to 32: 4th fault trip, faults 1 to 8
Index 33 to 40: 5th fault trip, faults 1 to 8
Index 41 to 48: 6th fault trip, faults 1 to 8
Index 49 to 56: 7th fault trip, faults 1 to 8
Index 57 to 64: 8th (oldest) fault trip, faults 1 to 8
The value 0 in index 1 means that no fault is active at the
present time. Further information for describing fault trips
is contained in r782, r949, P952. The fault memory is
deleted with the help of P952.
Dec.Plc.: 0
Unit: -
Indices: 64
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Faults/warnings
- Drive setting
- Upread/free access
r949
Fault Value
949
Visualization parameter for displaying fault values. Fault
values contain additional information on the faults which
have occurred and allow more exact diagnosis. The fault
values are assigned to the faults and are stored in the
same indices as the associated fault numbers in r947.
Indices 1 to 8: 1st (last) fault trip, fault values 1 to 8
Indices 9 to 16: 2nd fault trip, fault values 1 to 8
Indices 17 to 24: 3rd fault trip, fault values 1 to 8
Indices 25 to 32: 4th fault trip, fault values 1 to 8
Indices 33 to 40: 5th fault trip, fault values 1 to 8
Indices 41 to 48: 6th fault trip, fault values 1 to 8
Indices 49 to 56: 7th fault trip, fault values 1 to 8
Indices 57 to 64: 8th (oldest) fault trip, fault values 1 to 8
Further information on describing fault trips is contained in
in r782, r947, P952. The fault memory is deleted with the
help of P952.
Dec.Plc.: 0
Unit: -
Indices: 64
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Faults/warnings
- Drive setting
- Upread/free access
r951
FaultTextList
951
List of fault texts. Each fault text is stored under the index
corresponding to its fault.
Dec.Plc.: 0
Unit: -
Indices: 254
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Faults/warnings
- Upread/free access
P952*
# of Faults
952
Function parameters for displaying the stored fault trips
and for deletion of the fault memory. If 0 is entered, the
whole fault memory consisting of r782, r947, r949 is
deleted.
Init: 0
Min: 0
Max: 8
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Diagnostics
+ Faults/warnings
- Drive setting
- Upread/free access
Changeable in:
- Ready to switch on
r953
Warning Param 1
953
Visualization parameter for displaying which of warnings 1
to 16 are active.
Dec.Plc.: 0
Unit: -
Indices: -
Type: V2
Menus:
- Parameter menu
+ Diagnostics
+ Faults/warnings
- Upread/free access
118
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control