09.2008
Functions
Siemens AG
6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES
Compendium Motion Control
7-3
7.1.1.2 Processing
sequence
The time slots are processed in the sequence of their priority, whereby
time slot T0 has the highest priority and time slot T10 the lowest
priority. Each higher-priority time slot can interrupt a lower-priority time
slot.
The sequence control of the converters and inverters starts every time
slot automatically. If a higher-priority time slot is started, although
another time slot is being processed, the time slot having the lower
priority will be stopped and the time slot having the higher priority will
then be processed before the interrupted time slot can be further
processed.
Lower-priority time slots are lined up in a queue and are not processed
until all higher-priority time slots are finished.
2T0
3T0
4T0
0
Ti
m
e
s
lo
ts
Time
T0
Calculation of the blocks defined in T0
Calculation of the blocks defined in T1
Calculation of the blocks defined in T2
Calculation of the blocks defined in T3
All
blo
cks
d
efi
ne
d i
n
T0
p
ro
ce
ss
ed
All
blo
cks
d
ef
ine
d i
n
T1
p
ro
ce
ss
ed
Al
l b
lo
ck
s
de
fin
ed
in
T0
pr
oce
ss
ed
All b
lo
cks
d
ef
in
ed i
n
T0
p
ro
ce
ss
ed
A
ll b
loc
ks
de
fine
d i
n
T0
p
ro
ce
ss
ed
A
ll b
loc
ks
de
fine
d i
n
T1
p
ro
ce
ss
ed
All b
lo
ck
s
def
in
ed i
n
T2
p
ro
ce
ss
ed
Fig. 7-1
Processing sequence of the time slots