Parameter
Description
Data
Read/write
P105*
Mot.ShCirCurrent
105
Service parameter, only for Siemens service personnel.
This parameter is for special applications ONLY and must
not be changed for standard operation.
Short-circuit current of synchronous machine (only
required in field weakening operation)
In function diagram: 389.1
Init: 0,00
Min: 0,00
Max: 600,00
Unit: A
Indices: -
Type: O4
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P106*
Rev Field INDM
106
Function parameter for reversing the field of rotation on
induction motors:
If this parameter is set, the swapping of two terminals of
an induction motor can be compensated.
Init: ~
Min: 0
Max: 1
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P107*
Mot Rtd Freq
107
Function parameter for entering the rated motor frequency
for the connected induction motor. The rating-plate value
is to be entered.
Init: 50,0
Min: 10,0
Max: 500,0
Unit: Hz
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P108*
Mot Rtd Speed
108
Function parameter for entering the rated motor speed for
the connected induction motor. The rating-plate value is to
be entered.
Init: 3000
Min: 0
Max: 12000
Unit: 1/min
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P109*
Motor #PolePairs
109
Function parameter for entering the number of pole pairs
for the connected synchronous or induction motor.
In function diagram: 389.7, 390.7
Init: 2
Min: 1
Max: 110
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P111
Ls = f(Isd)
111
Function parameter for entering the support points of the
function Ls=f(isd) . The support points are expressed in p.
u. of the stator inductance at 40% of the rated motor
current (P102). The support points are subdivided in 10%,
20%, ..., 100% of the rated motor current.
Only for induction motors.
index1: 110,0
Min: 0,1
Max: 6553,5
Unit: %
Indices: 10
Type: O2
Menus:
- Parameter menu
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P113
Mot Rtd Torque
113
Function parameter for entering the rated motor torque for
the connected synchronous motor. The rating-plate value
is to be entered.
Entering this is absolutely necessary for synchronous
machine control. With the induction machine, the value is
only necessary for the calculation of the reference
torque/rated torque ratio. If the rated torque for an
induction machine is not known, the same values should
be entered in P113 and P354 (reference torque). For
example, the values of the factory setting can be left in
both parameters.
Init: 3,00
Min: 0,00
Max:
20000,00
Unit: Nm
Indices: -
Type: I4
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
13