Parameter
Description
Data
Read/write
U142
SmConnLmtMon 2
2142
Function parameter for entering the smoothing time
constants of the 2nd limit-value monitors with smoothing
(1 word).
Init: 0
Min: 0
Max: 10000
Unit: ms
Indices: -
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U143
HysConnLmtMon2
2143
Function parameter for entering the hysteresis of the 2nd
limit-value monitors with smoothing (1 word).
Init: 0,00
Min: 0,00
Max: 199,99
Unit: %
Indices: -
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U144*
ModeConnLmtMon2
2144
Function parameter for entering the mode of the 2nd limit-
value monitors with smoothing (1 word).
Init: 0
Min: 0
Max: 2
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
U145
FSDConnLmtMon1
2145
Function parameter for entering the fixed setpoint for the
1st limit-value monitor with smoothing (2 word).
Init: 0,00
Min: -200,00
Max: 200,00
Unit: %
Indices: -
Type: I4
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U146*
S.DConnLmtMon1
2146
BICO parameter for selecting the connector for the 1st
limit-value monitor with smoothing (2 word).
index1: 0
Unit: -
Indices: 2
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U147
SmDConnLmtMon1
2147
Function parameter for entering the smooothing time
constants of the 1st limit-value monitor with smoothing (2
word).
Init: 0
Min: 0
Max: 10000
Unit: ms
Indices: -
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U148
HysDConnLmtMon1
2148
Function parameter for entering the hysteresis of the 1st
limit-value monitor with smoothing (2 word).
Init: 0,00
Min: 0,00
Max: 199,99
Unit: %
Indices: -
Type: O4
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U149*
ModeDConnLmtMon
1
2149
Function parameter for entering the mode of the 1st limit-
value monitors with smoothing (2 word).
Init: 0
Min: 0
Max: 2
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
U150
FSDConnLmtMon2
2150
Function parameter for entering the fixed setpoint for the
2nd limit-value monitor without smoothing (2 word).
Init: 0,00
Min: -200,00
Max: 200,00
Unit: %
Indices: -
Type: I4
Menus:
- Parameter menu
+ Free blocks
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
138
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control