12.2010 Configuration
and Connection Examples
Siemens AG
6SE7087-6QX70 (Version AM)
SIMOVERT MASTERDRIVES
Compendium Motion Control
2-17
2.3.2 TB
boards
1. In the combination
CUPM
+
CBP
+ (
T100
or
T300
) no access to the
parameters of the T100 or T300 is possible via the PROFIBUS. This
only applies when the CBP is slotted into slot A or slot C.
Remedy: slot CBP into the adapter board (ADB) in slot G. See also
Catalog DA65.11, Chapter 6.
2. Basic device parameters cannot be read or altered via the USS
interface of the
T100
.
3. With the OP1S, TB parameters (
T100, T300
) can only be read and
altered if the parameter number is entered via the numerical keypad.
Access to parameter numbers is no longer possible with the "up"
and "down" keys if the next parameter does not exist.
4. If the
T300
is used together with the
SLB
in a single unit, The T300
with item no. 477 407 9000 02 must be product version B or higher.
All product versions can be used for item no. 477 407 9000 12.
5. If the
T100
is used together with the
SLB
in a single unit, T100 must
be product version L8 or higher.
2.3.3 EB
boards
EB1 connector 5103/monitoring parameters 662.3 (analog input
channel3) does
not
display the input of channel 3, but the input of
channel 2.
Slot EB1 into another slot (adapter board or slot C), or in the case of
item no. 477 491 9000 00, use product version B or higher. All product
versions can be used with item no. 477 491 9000 10.
EB1 item no.
477 491 9000 00 with
product vers. A on
slot A of the CUPM
Remedy