11.9.5
Selection of the braking resistor
The braking resistor is connected to the chopper of the rectifier unit.
During rating, it is assumed that the drives of the x and z axes can
brake simultaneously.
♦
The maximum braking power levels of the two inverters are
therefore added together.
P
P
kW
kW
kW
br
br Inv
max
.
.
.
=
= −
−
= −
∑
4 08
3 32
7 4
♦
For the mean braking power, the individual mean values are also
added together.
P
P
kW
kW
kW
br mean
br Inv mean
=
= −
−
= −
∑
0 146
0 28
0 426
.
.
.
♦
A 6SE7018-0ES87-2DC0 braking resistor of 80
Ω
with P
20
= 5 kW
is necessary.
P
kW
br max
.
=
7 4
<
15
7 5
20
.
.
⋅
=
P
kW
P
kW
br meen
=
0 426
.
<
P
kW
20
4 5
111
/ .
.
=