Parameter
Description
Data
Read/write
U526*
AutoSetInp
2526
This parameter enables a traversing data set to be
entered for the "Automatic" operating mode.
The parameter indices have the following significance
here:
Index 1: Program number (1 ... 20)
Index 2: Set number (1 ... 200)
Index 3: continuation ( 0 ... 19)
Index 4: 1st G-function
Index 5: 2nd G-function
Index 6: 3rd G-function
Index 7: 4th G-function
Index 8: Position setpoint (+/- 999 999 999)
Index 9: Traversing speed (0 ... MD Vmax)
Index 10: 1. M-number ( 0 ... 255)
Index 11: 2. M-number ( 0 ... 255)
Index 12: 3. M-number ( 0 ... 255)
Index 13: D-number ( 0 ... 20)
Index 14: UP-number (1 ... 20)
Index 15: Loop number (1 ... 65535)
All index values are zero in the presetting. Only the
relevant data have to be entered.
In connection with parameter U527, the following
functions can be executed:
U527=1 : Adoption of traversing data set from U526. After
adoption, all indices of U526 are deleted.
With U527=2 sets, programs and the entire program
memory can be deleted.
a) Deleting a traversing set:
U526.01=Program number, U526.02=set number, U527=2
b) Deleting a traversing program:
U526.01=program number, U526.02=255, U527=2
c) Deleting the entire program memory:
U526.01=255, U526.02=255, U527=2
U527=3: Teach in:
The current position is stored in the set which is selected
with U526 and U527.
U527=4: Acknowledgement of the positioning-specific
fault messages.
See parameter descriptions of P2525, P2527 .
index1: 0
Min: -
2147483647
Max:
2147483647
Unit: -
Indices: 15
Type: I4
Menus:
- Parameter menu
+ Technology
+ Positioning
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U527*
AutoSetAdopt
2527
With value 1, the automatic set is adopted from parameter
U526 is adopted.
With parameter value = 2, this set is deleted.
With defined values, the following functions can also be
tripped:
1. Delete set list
2. Delete program
3. Delete set.
See parameter descriptions P2525 and P2526.
Init: 0
Min: 0
Max: 9
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Technology
+ Positioning
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U528*
S.Encoder Select
2528
Selection of the encoder for position control in the case of
the encoder switchover roll feed function:
0: Position control with external encoder
1: Position control with motor encoder
Init: 0
Unit: -
Indices: -
Type: L2 ,B
Menus:
- Parameter menu
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
188
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control