Chapter 6: Using the Web Interface
139
In the Pressure Unit field, select "Pascal" or "psi" as the
measurement unit for pressure.
3. Click OK.
Configuring the Feature Port
The PX device supports connecting one of the following devices to its
FEATURE port:
Raritan Computer Interface Module (CIM) for KVM access. See
Dominion KX II Configuration
(on page 625).
Raritan asset management sensors (asset sensors). See
Connecting the Asset Management Sensor
(on page 43).
Raritan serial access products, including Dominion KSX II or SX.
See
Dominion KSX II or SX Configuration
(on page 630).
External beeper. See
Connecting an External Beeper
(on page
55).
Schroff
®
LHX-20, SHX-30 or LHX-40 heat exchanger. See
Connecting a Schroff LHX/SHX Heat Exchanger
(on page 55).
By default, the FEATURE port can automatically detect and display the
device connected to the FEATURE port. The only exception is the
Schroff
®
LHX/SHX device, which requires enabling the LHX/SHX support
before the PX can detect or display it. See
Managing the Schroff
LHX/SHX Heat Exchanger
(on page 315).
You can change the mode applied to the FEATURE port so that the PX
web interface only displays the device in the manner you wish.
To configure the FEATURE port:
1. Click the Feature Port folder. The Feature Port page opens in the
right pane.
2. Select the Port# 1 device on the Feature Port page, and click Setup.
The Feature Port Setup dialog appears.
3. Select the desired mode in the Detection Mode field.
Auto: The PX automatically detects and displays the device
connected to the FEATURE port. This is the default.
Disabled: The FEATURE port is disabled so the PX does not
detect and display the connected device.
A specific device type: The PX always displays the selected
device type no matter which device is connected or whether the
selected device is detected or not. After selecting a device type,
the Mode column shows "Pinned." Available device types are
listed below.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...