Chapter 4: Connecting External Equipment (Optional)
35
Using an Optional PX Sensor Hub
A Raritan sensor hub increases the number of connected DPX
environmental sensors per SENSOR port. Make sure the total number of
sensors connected to a SENSOR port does not exceed 32.
This hub supports DPX sensor packages only. Do NOT connect DPX2 or
DX sensor packages to the hub.
To connect DPX sensor packages via an optional sensor hub:
1. Connect a Raritan sensor hub to the PX device.
a. Plug one end of the Raritan-provided phone cable (4-wire, 6-pin,
RJ-12) into the IN port (Port 1) of the hub.
b. Get an RJ-12 to RJ-45 adapter. Connect this adapter's RJ-12
connector to the other end of the phone cable.
c. Connect this adapter's RJ-45 connector to the PDU's RJ-45
SENSOR port.
2. Connect DPX sensor packages to any of the four OUT ports on the
hub.
Raritan sensor hubs CANNOT be cascaded so at most one sensor
hub can be connected to each SENSOR port on the PX device. This
diagram illustrates a configuration with a sensor hub connected.
The PX device
RJ-12 to RJ-45 adapter
Raritan-provided phone cable
Raritan sensor hub
DPX sensor packages
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...