Chapter 6: Using the Web Interface
324
Updating the PX Firmware
When performing the firmware upgrade, the PX keeps each outlet's
power status unchanged so no server operation is interrupted. Outlets
that have been powered on prior to the firmware upgrade remain
powered on and outlets that have been powered off remain powered off
during and after the firmware upgrade.
You must be the system administrator or log in to the user profile with the
Firmware Update permission to update the PX firmware.
If applicable to your model, download the latest firmware file from the
Raritan website's
Support page
(
http://www.raritan.com/support/
),
read the release notes, then start the upgrade. If you have any questions
or concerns about the upgrade, contact Raritan Technical Support
BEFORE upgrading.
On a multi-inlet PDU (any model with X2 or X3 suffixes), all inlets must
be connected to the power source for the PDU to successfully upgrade
its firmware.
Warning: Do NOT perform the firmware upgrade over a wireless
network connection.
Firmware Update via Web Interface
After downloading the latest firmware, log in to the PX web interface to
upgrade the firmware.
Tip 1: Another alternative to update the firmware is via SCP. See
Firmware Update via SCP
(on page 552).
Tip 2: If you have a large number of PX devices to update and a TFTP
server is available, you can choose to perform the firmware upgrade via
TFTP in a DHCP network. See
Bulk Configuration or Firmware
Upgrade via DHCP/TFTP
(on page 526).
To update the firmware:
1. Choose Maintenance > Update Firmware. The Update Firmware
dialog appears.
2. In the Firmware File field, click Browse to select an appropriate
firmware file.
3. Click Upload. A progress bar appears to indicate the upload status.
4. When the upload is complete, version information of both the existing
firmware and uploaded firmware is shown, providing you a last
chance to terminate the update.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...