Chapter 4: Connecting External Equipment (Optional)
34
DPX Sensor Packages
Most DPX sensor packages come with a factory-installed sensor cable,
whose sensor connector is RJ-12.
The supported maximum distance is 98 feet (30 m). See
Supported
Maximum DPX Sensor Distances
(on page 37) for further illustrations.
To directly connect a DPX with a factory-installed sensor cable:
An RJ-12 to RJ-45 adapter is required to connect a DPX sensor package
to the PX3.
a. Connect the adapter's RJ-12 connector to the DPX sensor cable.
b. Connect the adapter's RJ-45 connector to the RJ-45 SENSOR
port of the PX3.
To directly connect a differential air pressure sensor:
1. Connect a Raritan-provided phone cable to the IN port of a
differential air pressure sensor.
2. Get an RJ-12 to RJ-45 adapter. Connect the adapter's RJ-12
connector to the other end of the phone cable.
3. Connect this adapter's RJ-45 connector to the RJ-45 SENSOR port
on the PX3.
Note: You can cascade multiple differential air pressure sensors using
Raritan-provided phone cables. For details, refer to the Environmental
Sensors Guide or Online Help on Raritan website's
PX2 Support Files
page
(
https://www.raritan.com/support/product/px2/px2-support-files
).
When cascading air pressure sensors, remember that a SENSOR port
supports a maximum of 32 sensors.
The PX device
Raritan differential air pressure sensors
RJ-12 to RJ-45 adapter
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...