Appendix G: PX Models with Residual Current Monitoring
582
6. After completing the RCM self-test, the LCD display indicates the
RCM self-test result: passed or failed.
7. Press
or
to return to the RCM information page.
8. Do one of the following:
To perform RCM self-test for additional inlets, press
or
to select a different inlet and repeat the same steps.
To return to the Main Menu, press
.
PX3 phase I models:
1. Press the MODE button until the LCD alternates between "SLF" and
"tSt," which means
SELF TEST
.
2. Press the FUNC button to start RCM self-test.
3. The LCD shows dash symbols during RCM self-test.
4. Upon completion, RCM self-test results are displayed for 30 seconds,
or until you press any button.
PAS: Self-test passed.
FAL: Self-test failed (the PX also beeps).