Chapter 6: Using the Web Interface
263
Any numeric sensor's reading moves past any threshold into the
warning or critical range.
Any sensor reading or state returns to normal.
Any sensor becomes unavailable.
The active energy sensor is reset.
Any discrete sensor changes its state -- either from normal to
alarmed or from alarmed to normal.
For example, when the outlet 3's voltage crosses into the upper
warning range, the SNMP notifications are sent, and when the
voltage drops below the upper warning threshold, the SNMP
notifications are sent again.
Sample Inlet-Level Event Rule
In this example, we want the PX to send SNMP notifications to the
SNMP manager for any sensor change event of the Inlet I1.
Note: The SNMP notifications may be SNMP v2c or SNMP v3 traps or
informs, depending on the settings for the System SNMP Notification
Action. See
Configuring SNMP Notifications
(on page 332).
The event rule is set like this:
Event: Inlet > Inlet I1 > Sensor > Any sub-event
Actions: System SNMP Notification Action
To create the above event rule:
1. Select Event > Inlet to indicate we are specifying an event at the inlet
level.
2. Select "Inlet I1" from the submenu because that is the inlet in
question.
3. Select "Sensor" to refer to sensor events.
4. Select "Any sub-event" because we want to specify all events related
to all types of inlet sensors and thresholds, such as current, voltage,
upper critical threshold, upper warning threshold, lower critical
threshold, lower warning threshold, and so on.
5. Select "System SNMP Notification Action" to send SNMP
notifications to respond to the specified event.
Then the SNMP notifications are sent when:
Any numeric sensor's reading moves past any threshold into the
warning or critical range.
Any sensor reading or state returns to normal.
Any sensor becomes unavailable.
The active energy sensor is reset.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...