Chapter 8: Using the Command Line Interface
469
config:#
sensor inletpole <n> <p> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current
Current sensor
voltage
Voltage sensor
activePower
Active power sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Note: If the requested sensor type is not supported, the "Sensor is
not available" message is displayed.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the specified threshold for the specified
inlet pole sensor.
disable
Disables the specified threshold for the specified
inlet pole sensor.
A numeric
value
Sets a value for the specified threshold of the
specified inlet pole sensor and enables this
threshold at the same time.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...