Chapter 6: Using the Web Interface
296
Tip: The same asset sensor's page can be also opened by clicking
Feature Port in the left pane, and then double-clicking the asset
sensor in the right pane.
3. Click Setup. The setup dialog for the asset sensor appears.
Tip: You can also trigger the same dialog by clicking Asset
Management in the left pane, and then clicking Asset Strip Setup or
double-clicking the asset sensor in the right pane.
4. To rename the asset sensor, type a new name in the Name field.
5. In the "Number of Rack Units" field, type the total number of rack
units supported by the AMS. Default is 48.
6. Here, rack units are the number of asset management tag ports on
the asset management strip. For example, if the AMS has 48 asset
management tag ports, it supports up to 48 rack units on a cabinet.
7. Determine how to number all rack units on the asset sensor by
selecting an option in the Numbering Mode.
Top-Down: The rack units are numbered in the ascending order
from the highest to the lowest rack unit.
Bottom-Up: The rack units are numbered in the descending order
from the highest to the lowest rack unit.
8. In the Numbering Offset field, select the starting number. For
example, if you select 3, the first rack unit is numbered 3, the second
is numbered 4, the third is numbered 5, and so on until the final
number.
9. Indicate how the asset sensor is mounted on the rack in the
Orientation field. The rack unit that is most close to the RJ-45
connector of the asset sensor will be marked with the index number
1 in the web interface.
For the latest version of asset sensors with a built-in tilt sensor, it is
NOT necessary to configure the orientation setting manually. The PX
device can detect the orientation of the asset sensors and
automatically configure it.
Top Connector: This option indicates that the asset sensor is
mounted with the RJ-45 connector located on the top.
Bottom Connector: This option indicates that the asset sensor is
mounted with the RJ-45 connector located at the bottom. Click
OK.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...