Chapter 8: Using the Command Line Interface
359
Outlet Sensor Threshold Information
This command syntax shows the specified outlet sensor's
threshold-related information.
#
show sensor outlet <n> <sensor type>
To show detailed information, add the parameter "details" to the end of
the command.
#
show sensor outlet <n> <sensor type>
details
Variables:
<n> is the number of the outlet whose sensors you want to query.
<sensor type> is one of the following sensor types:
Sensor type
Description
current
Current sensor
voltage
Voltage sensor
activePower
Active power sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
lineFrequency
Line frequency sensor
Displayed information:
Without the parameter "details," only the sensor reading, state,
threshold, deassertion hysteresis and assertion timeout settings of
the specified outlet sensor are displayed.
With the parameter "details," more sensor information is displayed,
including resolution and range.
If the requested sensor type is not supported, the "Sensor is not
available" message is displayed.