![Raritan PX3-4000 series User Manual Download Page 409](http://html1.mh-extra.com/html/raritan/px3-4000-series/px3-4000-series_user-manual_3742180409.webp)
Chapter 8: Using the Command Line Interface
388
Examples
This section illustrates several PDU configuration examples.
Example 1 - PDU Naming
The following command assigns the name "my px12" to the PDU.
config:#
pdu name "my px12"
Example 2 - Outlet Sequence
The following command causes a 10-outlet PDU to first power on the 8th
to 6th outlets and then the rest of outlets in the ascending order after the
PDU powers up.
config:#
pdu outletSequence 8-6,1-5,9,10
Example 3 - Outlet Sequence Delay
The following command determines that the outlet 1's delay is 2.5
seconds, outlet 2's delay is 3 seconds, and the delay for outlets 3
through 5 is 10 seconds.
config:#
pdu outletSequenceDelay 1:2.5;2:3;3-5:10
Example 4 - Non-Critical Outlets
The following command sets outlets 1, 2, 3, 7, and 9 to be critical outlets,
and 4, 5, 6, 8, 10, 11 and 12 to be non-critical outlets on a 12-outlet PX.
config:#
pdu nonCriticalOutlets 1-3,7,9:false;4-6,8,10-12:true
Network Configuration Commands
A network configuration command begins with
network
. A number of
network settings can be changed through the CLI, such as the IP
address, transmission speed, duplex mode, and so on.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...