Appendix G: PX Models with Residual Current Monitoring
579
Checking RCM States on Phase II Models
Unlike PX3 phase I models, which show RCM information on the LCD
display only when there is an RCM critical alarm, PX3 phase II models
allow you to retrieve RCM information from the LCD display even though
there is no RCM alarm.
To check RCM information on PX3 phase II LCD display:
1. Press
or
to access the
Main Menu
(on page 63).
2. Press
or
to select "Residual Current", and press
.
3. The LCD display shows two types of information for Inlet 1.
RCM state: Normal or Warning.
RCM reading: Residual current value in Amps.
If your PX has more than one inlet, a list of inlets is displayed, along
with each inlet's RCM state and reading.
4. To return to the Main Menu, press
.