Appendix G: PX Models with Residual Current Monitoring
576
Setting RCM Current Thresholds
The RCM current thresholds define the critical, warning and normal
range of residual current.
To configure the RCM current thresholds and run self-test:
1. Click Inlet I1 to open the Inlet page.
2. Click Setup to set up RCM thresholds.
3. Residual current greater than this value triggers Critical RCM state.
4. Enable or disable the RCM critical threshold.
5. Residual current greater than this value triggers Warning RCM state.
6. Enable or disable the RCM warning threshold.
7. Residual current decrease to end Warning or Critical RCM state.
8. Click 'Self test' to run RCM self-test.
Scheduling RCM Self-Test
You can have the PX run RCM self-test automatically at a regular time
interval or on a specific date and time. See
Scheduling an Action
(on
page 248) for the procedure and select "Start residual current monitor
self test" to create the scheduled RCM self-test action.