Chapter 4: Connecting External Equipment (Optional)
39
The following procedure illustrates a DPX2 sensor cable with three head
connectors. Your sensor cable may have fewer head connectors.
Warning: If there are free head connectors between a DPX2 sensor
cable's RJ-12 connector and the final attached DPX2 sensor, the
sensors following the free head connector(s) on the same cable do
NOT work properly. Therefore, always occupy all head connectors
prior to the final sensor with a DPX2 sensor.
To connect a DPX2 sensor package to the PX:
1. Connect a DPX2 sensor to the first head connector of the DPX2
sensor cable.
2. Connect remaining DPX2 sensors to the second and then the third
head connector.
Tip: If the number of sensors you are connecting is less than the
number of head connectors on your sensor cable, connect them to
the first one or first two head connectors to ensure that there are NO
free head connectors prior to the final DPX2 sensor attached.
3. Use an RJ-12 to RJ-45 adapter to connect a DPX2 sensor package
to the PX3.
a. Connect the adapter's RJ-12 connector to the DPX2 sensor
cable.
b. Connect the adapter's RJ-45 connector to the RJ-45 SENSOR
port of the PX3.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...