Chapter 2: Rack-Mounting the PDU
9
3. Screw a button in the screw hole near the bottom. The
recommended torque for the button is 1.96 N·m (20 kgf·cm).
4. Screw a button in the screw hole near the top. The recommended
torque for the button is 1.96 N·m (20 kgf·cm).
5. Ensure that the two buttons can engage their mounting holes in the
rack or cabinet simultaneously.
6. Press the PX device forward, pushing the mounting buttons through
the mounting holes, then letting the device drop slightly. This secures
the PX device in place and completes the installation.
Mounting 1U or 2U Models
Using the appropriate brackets and tools, fasten the 1U or 2U PX device
to the rack or cabinet.
To mount the PX device:
1. Attach a rackmount bracket to both sides of the PX with the provided
screws.
2. Insert the cable-support bar into rackmount brackets.