Chapter 3: Installation and Configuration
31
Tip: The USB-cascading configuration can be a combination of diverse
Raritan products that support the USB-cascading feature, including PX2,
PX3, PX3TS, EMX and BCM. For details, see the
USB-Cascading
Solution Guide
, which is available on the
PX2 web page
(
http://www.raritan.com/support/product/px2/
).
Installing Cable Retention Clips on Outlets (Optional)
If your PX device is designed to use a cable retention clip, install the clip
before connecting a power cord. A cable retention clip prevents the
connected power cord from coming loose or falling off.
The use of cable retention clips is highly recommended for regions with
high seismic activities, and environments where shocks and vibrations
are expected.
These optional clips come in various sizes to accommodate diverse
power cords used on IT equipment, which are connected to C13 or C19
outlets. You can request a cable retention kit containing different sizes of
clips from you reseller. Make sure you use a clip that fits the power cord
snugly to facilitate the installation or removal operation (for servicing).
Note: Some NEMA sockets on PSE-certified PDUs for Japan have
integral locking capability and do not need cable retention clips. See
Locking Outlets and Cords
(on page 641).
To install and use a cable retention clip on the outlet:
1. Locate two tiny holes at two sides of an outlet.
2. Install the cable retention clip by inserting two ends of the clip into
the tiny holes.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...