510
CompoNet Explicit Messages
Appendix A
Setting Hold/Clear for Communications Errors for Outputs
Note
The default setting is for all outputs to be cleared (0).
Monitoring Power Short-circuit Detection (Slave Units with Input Short-
circuit and Disconnected Line Detection)
Note
The response data size is 1 byte for 8 inputs, 2 bytes for 16 inputs, or 4 bytes for 32 inputs.
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service
data
Attribute
ID
Data
Setting for
Output Sta-
tus (Hold or
Clear) after
Communi-
cations
Error
Read Reads whether hold or
clear is set as the output
status after a communi-
cations error for an out-
put (No. 1 to 32)
specified by the Instance
ID. The setting can be
read for a specified num-
ber of points.
0E hex
09 hex
01 to 20
hex
05 hex
---
1 byte
00 hex:
Clear
01 hex: Hold
Setting for
Output Sta-
tus (Hold or
Clear) after
Communi-
cations
Error
Write
Sets whether hold or
clear is set as the output
status after a communi-
cations error for an out-
put (No. 1 to 32)
specified by the Instance
ID. The setting can be
set for a specified num-
ber of points.
10 hex
09 hex
01 to 20
hex
05 hex
1 byte
00 hex: Clear
01 hex: Hold
---
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service
data
Attribute
ID
Data
Power
Short-cir-
cuit Detec-
tion
Read Reads the sensor power
supply short-circuit sta-
tus for the input (No. 1 to
32) specified by the
Instance ID.
0E hex
08 hex
01 to 20
hex
69 hex
---
1 byte
00 hex: Nor-
mal
01 hex:
Short-circuit
Power
Short-cir-
cuit Status
for all Slave
Units Read
at Once
Read Reads the sensor power
supply short-circuit sta-
tus for all Slave Units.
0E hex
1D hex
01 hex
67 hex
---
1 byte,
2 bytes, or
4 bytes
00 hex: Nor-
mal
Other than
00 hex: Sen-
sor power
supply
short-circuit
for applica-
ble terminal
(Inputs 0 to
31: Bits 0 to
31) (See
note.)
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...