331
Monitoring Temperature Data
Section 7-4
7-4
Monitoring Temperature Data
The Monitor Window of the CX-Integrators can be used to monitor the set val-
ues and current status of temperature data, and to check Unit maintenance
information.
With the CX-Integrator connected online, right-click a Temperature Input Unit
icon in the Network Configuration Window and select
Monitor
from the pop-
up menu to display the Monitor Window. The check boxes (flags) shown in the
following table will be selected if the corresponding error had occurred.
Refer to
11-1 CX-Integrator
on page 398 for details on the CX-Integrator.
Monitor Window
General Tab Page
Item
Description
Monitor
Display
Comment
Displays the text set as the Unit comment.
Last Mainte-
nance Date
Displays the last maintenance date that was set.
Present Unit Con-
duction Time
Displays the total time that the Unit has been ON
(cumulative power ON time).
Present Network
Power Voltage
Displays the present network power supply voltage.
Network Power
Voltage (Peak)
Displays the maximum and minimum network power
supply voltages up to the present time.
Network Power
Voltage (Bottom)
Status
Check
Boxes
Unit Maintenance Selected if the total Unit conduction time has exceed
the monitor value set by the Unit Conduction Time
Monitor Function.
Network Power
Voltage Drop
Selected if the network power supply voltage has
fallen below the monitor value set by the Network
Power Voltage Monitor Function.
Cumulated
Counter Over
Selected if any of the input's cumulative time counter
values has exceeded the monitor value set by the
Temperature Integration Function.
EEPROM Data
Error
Selected if a Unit Error has occurred in the Unit
memory.
Temperature
Resistance Sen-
sor Disconnected
Selected if a Temperature Resistance Sensor Dis-
connection error has occurred.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...