150
Units with Screw Terminal Blocks
Section 5-3
5-3-10 Eight-point Input Units (3-tier Terminal Block)
CRT1-ID08TA/CRT1-ID08TA-1/CRT1-ID08TAH/CRT1-ID08TAH-1
Input Section Specifications
Component Names and Functions (Same for CRT1-ID08TA(-1)/CRT1-ID08TAH(-1))
Item
Specification
Model
CRT1-ID08TA
CRT1-ID08TA-1
CRT1-ID08TAH-1
CRT1-ID08TAH-1
I/O capacity
8 inputs
Internal I/O common
NPN
PNP
NPN
PNP
ON voltage
15 VDC min.
(between each
input terminal and
the V terminal)
15 VDC min.
(between each
input terminal and
the G terminal)
10.5 VDC min.
(between each
input terminal and
the V terminal)
10.5 VDC min.
(between each
input terminal and
the G terminal)
OFF voltage
5 VDC max.
(between each
input terminal and
the V terminal)
5 VDC max.
(between each
input terminal and
the G terminal)
---
---
OFF current
1.0 mA max.
Input current
At 24 VDC: 6.0 mA max./input
At 17 VDC: 3.0 mA min./input
ON delay
1.5 ms max.
OFF delay
1.5 ms max.
Power supply short-circuit detection
---
Operates at 50 mA/point min.
Disconnection detection
---
Operates at 0.3 mA/point max.
Number of circuits per common
8 inputs/common
Isolation method
Photocoupler
Input indicator
LED (yellow)
Installation
DIN Track
Power supply type
Multi-power supply
Current supplied to input devices
100 mA/points
50 mA/point
Communications power supply cur-
rent consumption
30 mA max. for 24-VDC power supply
voltage
50 mA max. for 14-VDC power supply
voltage
35 mA max. for 24-VDC power supply
voltage
60 mA max. for 14-VDC power supply
voltage
I/O power supply current consump-
tion
5 mA max. for 24-VDC power supply
voltage
25 mA max. for 24-VDC power supply
voltage
Weight
190 g max.
200 g max.
Communications
indicators:
MS and NS
Node address switches:
×
10 and
×
1 (from left)
Communications connector
I/O terminal block (removable)
Input indicators
0 to 7
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...