338
Temperature Input Units
Section 7-5
Note
If the settings are incorrect, the MS Indicator will flash red and the
Unit will not operate. In this case, make the settings again and reset
the power supply.
CRT1-TS04P
Note
If the settings are incorrect, the MS Indicator will flash red and the
Unit will not operate. In this case, make the settings again and reset
the power supply.
Note
1.
Always set pin 5 and pin 7 to OFF (default).
2.
Always set pin 8 to ON if the DIP switch is used to set the ranges. If this pin
is OFF, the DIP switch settings will not be enabled.
3.
The DIP switch settings are read when the power is turned ON.
4.
°
C/
°
F display settings cannot be set individually for each input.
Setting Using the CX-
Integrator
Input types can be set for each temperature input using the CX-Integrator.
Use the following procedure.
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the tab for the input where the input type is to be set and select an
input type in the
Input Type
Field.
OFF
ON
OFF
ON
U
ON
ON
OFF
ON
N
OFF
OFF
ON
ON
W
ON
OFF
ON
ON
B
OFF
ON
ON
ON
PL2
ON
ON
ON
ON
Not used.
SW1
SW2
SW3
SW4
Input type
Always
OFF
OFF
Always OFF.
PT100 (
−
200 to 850
°
C)
ON
PT100 (
−
200 to 200
°
C)
SW1
SW2
SW3
SW4
Input type
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...