89
Connecting External I/O for Slave Units
Section 3-6
3-6-1
Connecting to a Screw Terminal Block
For Slave Units with screw terminal blocks, attach the following M3 crimp ter-
minals to signal lines and then connect them to the terminal block.
Tighten the terminal block screws to a torque of 0.5 N·m.
3-6-2
Connecting to e-CON Connector Terminals
For Slave Units with e-CON connector terminals, a special cable connector
must be attached to an external device cable. Follow the procedure below to
attach the connector to the cable.
■
Checking the Cable Connector and Cable Wire Size
The wire size and sheath diameter of applicable cables depend on the type of
cable connector. Use the following table to check that the cable connector and
external device cable wire size and sheath diameter are compatible.
Tyco Electronics Connectors
Sumitomo 3M Connectors
Analog I/O Slave Units
CRT1-AD04
Screw terminal block
(M3)
CRT1-DA02
Temperature Input Units
CRT1-TS04T
CRT1-TS04P
Expansion Units
XWT-ID08(-1)
XWT-OD08(-1)
XWT-ID16(-1)
XWT-OD16(-1)
Bit Slaves
With e-CON Connectors
CRT1B-ID02S(-1)
e-CON connector
CRT1B-OD02S(-1)
IP54
CRT1B-ID02SP(-1)
CRT1B-OD02SP(-1)
CRT1B-ID04SP(-1)
With Screw-less Clamp Termi-
nal Blocks
IP54
CRT1B-MD04SLP(-1)
Screw-less clamp termi-
nal block
Name
Model
I/O connection method
6.0 mm max.
6.0 mm max.
Model
Housing color
Applicable wire range
3-1473562-4 Orange
sheath outer diameter: 0.9 to 1.0 mm
Cross-sec-
tional area:
0.08 to
0.5 mm
2
1-1473562-4 Red
sheath outer diameter: 0.9 to 1.0 mm
1473562-4
Yellow
sheath outer diameter: 1.0 to 1.15 mm
2-1473562-4 Blue
sheath outer diameter: 1.15 to 1.35 mm
4-1473562-4 Green
sheath outer diameter: 1.35 to 1.60 mm
Model
Housing color
Applicable wire range
37104-3101-000FL
Red
AWG26 (0.14 mm
2
) to AWG24 (0.2 mm
2
),
sheath outer diameter: 0.8 to 1.0 mm
37104-3122-000FL
Yellow
AWG26 (0.14 mm
2
) to AWG24 (0.2 mm
2
),
sheath outer diameter: 1.0 to 1.2 mm
37104-3163-000FL
Orange
AWG26 (0.14 mm
2
) to AWG24 (0.2 mm
2
),
sheath outer diameter: 1.2 to 1.6 mm
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...