CRT1B-OD02SP/CRT1B-OD02SP-1
Output Section Specifications
Note
The current consumption is for Bit Slave Unit communications cur-
rent when all outputs are OFF, i.e., it does not include the output de-
vice load current consumption. The communications power supply
is also used for the I/O power supply for actuators. Be sure to con-
sider the actuator load current consumption and the number of sen-
sors connected in addition to the communications power. The
power supply current consumption is expressed by the following
formula.
Communications power supply current consumption = Bit Slave
Unit communications current consu (actual load current
×
number of actuators used)
Item
Specification
Model
CRT1B-OD02SP
CRT1B-OD02SP-1
I/O capacity
2 outputs
Internal I/O common
NPN
PNP
Rated output current
0.2 A/output
Load power supply voltage
Communications power supply voltage 0 V (max.)
Communications power supply voltage
−
1.2 V (min.)
Residual voltage
1.2 V max. (0.2 A DC, between each
output terminal and BS
−
)
1.2 V max. (0.2 A DC, between each
output terminal and BS+)
Leakage current
0.1 mA max.
ON delay
0.5 ms max.
OFF delay
1.5 ms max.
Number of circuits per common
2 outputs/common
Load power short-circuit detection Supported.
Isolation method
No isolation
Output indicators
LEDs (yellow)
Degree of protection
IEC standard IP54
Installation
Screw installation (M4)
Power supply type
Network power supply
Communications power supply
current consumption (See note.)
50 mA max. for 24-VDC power supply voltage
75 mA max. for 14-VDC power supply voltage
Weight
169 g max.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...