478
Temperature Input Unit Functions
Section 11-5
11-5-14 User Adjustment
This function can be used to compensate for offsets in the input value caused
by factors such as the characteristics and connection methods of the input
sensor.
Note
1.
Temperature Input Units are properly adjusted at the factory before ship-
ment, so it is normally unnecessary to make adjustments. Use the User
Adjustment function only when absolutely necessary. OMRON is not re-
sponsible for the results of user adjustments. If a mistake is made in the
adjustments, the adjustment data can be cleared to return to the factory
default settings.
2.
The Temperature Input Unit continues the temperature conversion opera-
tions even after user adjustments have been made. It is possible for tem-
perature data values to change suddenly from previous values after the
user adjustments are made, so always consider the effects on the operat-
ing environment before applying user adjustments.
100%
0%
Temperature
input value
Conversion data
After
adjustment
Before
adjustment
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...