476
Temperature Input Unit Functions
Section 11-5
Note
The following table shows the time divisions and number of measurements.
Setting Using CX-Integrator
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the tab for the input where the cumulative counter is to be set, and
select the
Cumulated Count
Check Box in the
Function Choice
Area.
4.
To set the counter unit, click the
Cumulated Count
Tab and select
Hour
or
Minute
in the
Cumulated Timer
Field.
Integral value
(
°
C
×
hours or
°
C
×
minutes)
Time division
(See note.)
Temperature
input value
Time
Units
Time division
Number of measurements
Hours
12 seconds
300
Minutes
200 ms
300
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...