307
Analog Input Slave Units
Section 6-4
The details of each byte are shown in the following table.
Note
The one-shot time can be changed. For details, refer to the one-shot time set-
tings for the top/valley hold function.
Analog Status Flags
The Analog Status Flags include allocations for the Comparator Result Flag,
the Top/Valley Detection Timing Flags, and the Disconnected Line Detection
Flags. These flags are used for detection and monitoring.
The data format used for each byte when these flags are allocated in the Mas-
ter Unit is shown below (4 bytes = 2 words).
The details for each bit are shown in the following table.
Byte
Abbreviation
Name
Details
+0
V_STx
Valley Detection Tim-
ing Flag
Turns ON when a valley is
detected by the valley hold
function and then turns OFF
after the one-shot time has
elapsed.
+1
T_STx
Top Detection Timing
Flag
Turns ON when a top is
detected by the top hold func-
tion and then turns OFF after
the one-shot time has elapsed.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
BW0
T_ST0 V_ST0
HH0
H0
PS0
L0
LL0
Input
0
+1
BW1
T_ST1 V_ST1
HH1
H1
PS1
L1
LL1
Input
1
+2
BW2
T_ST2 V_ST2
HH2
H2
PS2
L2
LL2
Input
2
+3
BW3
T_ST3 V_ST3
HH3
H3
PS3
L3
LL3
Input
3
Bit
Abbrevi-
ation
Name
Details
0
LLx
Compara-
tor result
Low Low Limit
Alarm Flag
Turns ON when the value of data
allocated in Analog Data drops
below the Low Low Limit alarm set-
ting.
1
Lx
Low Limit Alarm
Flag
Turns ON when the value of data
allocated in Analog Data drops
below the Low Limit alarm setting.
2
PSx
Normal Flag
(pass signal)
Turns ON when none of the alarms
(High High Limit, High Limit, Low
Low Limit, and Low Limit) have been
output.
3
Hx
High Limit
Alarm Flag
Turns ON when the value of data
allocated in Analog Data exceeds
the High Limit alarm setting.
4
HHx
High High Limit
Alarm Flag
Turns ON when the value of data
allocated in Analog Data exceeds
the High High Limit alarm setting.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...