484
Temperature Input Unit Functions
Section 11-5
Note
1.
The bias compensation value may not be accepted if there is a large tem-
perature difference between the Terminal Block and ZERO-CON (0
°
C
bath). If this problem occurs, correct the adjustment system by using a
ZERO-CON compatible with the sensor being adjusted or other means.
2.
Always test the indication accuracy after making user adjustments to verify
that the adjustments are correct. Test the indication accuracy at three
points: the lower limit value, an intermediate value, and the upper limit val-
ue.
• Connect the external devices as shown in the following diagram.
• After verifying that the ZERO-CON is set to 0
°
C, set the STV’s output
voltage to produce a voltage equivalent to the test voltage.
Note
Always use the compensating conductors (the same kind that will be
used with the sensor being adjusted) to connect the ZERO-CON to
the CRT2-TS04T’s input terminals.
STV
INPUT
OUTPUT
CRT1-TS04T
Compensating
conductors
ZERO-CON
(0
°
C bath)
Input (+)
Input (–)
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...